Designing with NeXTimber acoustic systems
NeXTimber (by Timberlink Australia Pty Ltd) manufactures NeXTimber cross-laminated timber. Timberlink commissioned laboratory sound-insulation testing of systems incorporating NeXTimber CLT at the CSIRO Acoustic Laboratory, assessed by PKA Acoustic Consulting. SPEC Toolbox carries the resulting floor build-ups so NeXTimber CLT floors can be designed against the sound-insulation requirements of the National Construction Code.
The integration covers ten NeXTimber acoustic floor build-ups, each assembled over the NeXTimber NX5/150 cross-laminated timber panel (150 mm, nominal density 500 kg/m3, areal mass 75 kg/m2), from the following layers.
Isolation
Floor substrate and finish
Battens, pedestals and cavity
At a glance, the NeXTimber acoustic systems support:
The NeXTimber acoustic systems are available in the SPEC Toolbox acoustic floor design:
The airborne and impact ratings are taken from the integrated database of tested build-ups; the bare NeXTimber panel is also carried (NX5/150: Rw 39, Ctr -4, Rw+Ctr 35, STC 39, Ln,w 87, IIC 22), so the contribution of the build-up over the bare panel is clear. Three of the build-ups – the two Tarkett vinyl systems and the cushion-backed carpet tile over the TATE access floor – carry impact ratings only. Field performance depends on installation and flanking, which the acoustic consultant verifies.
Performance is established by laboratory test and assessment, not by structural calculation. Timberlink commissioned the CSIRO Acoustic Laboratory (Clayton, Victoria) to test systems incorporating NeXTimber CLT, and PKA Acoustic Consulting assessed the results to give the performance of each build-up. Airborne insulation is rated to AS/NZS ISO 717.1:2004 (Rw, with the Ctr spectrum adaptation term) and ASTM E413-16 (STC); impact insulation is rated to AS ISO 717.2 (2004) (Ln,w, with CI) and ASTM E989-89 (IIC). The integrated values are those held in the SPEC Toolbox acoustic database, each build-up carrying its full one-third-octave band data from 50 to 5000 Hz alongside the single-number ratings. The relevant sound-insulation requirements are in the National Construction Code Volume 1 Section F7; for floors separating sole-occupancy units the deemed-to-satisfy provisions require Rw+Ctr at least 50 and Ln,w no more than 62. The ratings are laboratory values: they make no allowance for flanking transmission in field installation, and the acoustic engineer confirms the details for the project.
It is written against the SPEC Toolbox acoustic database (edition 6 February 2026), which holds the integrated build-ups and their ratings. The underlying testing was carried out at the CSIRO Acoustic Laboratory and assessed by PKA Acoustic Consulting. Values are re-checked against the database before the integrated data changes.
Ten floor build-ups over the NeXTimber NX5/150 panel: raised batten systems on REGUPOL pads with Scyon Secura, Red Tongue or Yellow Tongue substrates; a direct REGUPOL sheet underlay system; and TATE raised access floor systems on pedestals with REGUPOL pads – in bare, carpet-tile and vinyl finishes.
Across the integrated build-ups the airborne rating runs from Rw 47 to 55 (Rw+Ctr 40 to 52, STC 47 to 55) and the impact rating from IIC 43 to 52 (Ln,w 54 to 67), depending on the substrate, the isolation layer, the cavity insulation and the floor finish. The bare NX5/150 panel alone rates Rw 39 (Rw+Ctr 35) and Ln,w 87 (IIC 22).
All ten build-ups are over the NeXTimber NX5/150 cross-laminated timber panel – 150 mm thick, nominal density 500 kg/m3, areal mass 75 kg/m2. The integrated ratings apply to that panel; a different panel thickness changes the assembly and would need its own assessment.
The National Construction Code Volume 1 Section F7 deemed-to-satisfy provisions require Rw+Ctr at least 50 and Ln,w no more than 62 for floors separating sole-occupancy units. Several of the integrated build-ups meet both; the calculator reports the rating for the selected build-up so it can be checked against the requirement for the project.
Three of the ten build-ups – the two Tarkett Tapiflex vinyl systems and the cushion-backed ATF carpet tile over the TATE access floor – carry impact ratings (Ln,w and IIC) in the integrated data but no airborne rating, because the finish was tested for its effect on impact sound over an already-rated base system.